Psychrometry
Water vapour pressure as function of temperature, wet-bulb temperature, and air pressure

e = water-vapour pressure [hPa]
(after Smithsonian Meteorological Tables, 1984)

e(T) = e(Tw) - 6.6·10-4 (1 + 1.15· 10-3Tw) p |T-Tw|


T = temperature [°C]
e(Tw) = saturation vapour pressure at Tw [Pa]
Tw = wet-bulb temperature [°C]
p = pressure [Pa]

R = e / E = relative humidity
E = saturation vapour pressure at T [hPa]


Calculation of wet-bulb temperature (coarse approximation for p = 1013.25 hPa)
(after R. Stull, J. Appl. Meteor. and Clim., 2011)

Tw = T atan[0.151977(R + 8.313659)1/2] + atan(T + R) - atan(R - 1.676331)
     + 0.00391838 R3/2 atan(0.023101 R) - 4.686035     (T in °C and R in %)


Vapour pressure and relative humidity calculation T: °C      Tw: °C      p: hPa   

e: hPa

R: %

Wet-bulb temperature calculation (only for p=1013.25 hPa) T: °C      R: %     

Tw: °C